Fire Dampers and Access Doors in a Ductwork Takeoff

Fire dampers and access doors are small items that sink ductwork margins when they are missed. Where they go, which standards apply, and how to count them from the drawings and the spec.

Customiser team5 min read

Key takeaways

  • A fire damper closes a duct where it passes through a fire-resisting wall or floor, to keep fire from spreading through the ductwork.
  • In the UK, fire dampers are product-standard to BS EN 15650 and fire-tested to BS EN 1366-2; in the US, UL 555 covers fire dampers and UL 555S smoke dampers.
  • Every fire damper needs an access door so it can be inspected and reset, so count them together.
  • Further access doors come from DW/144 and TR19 for cleaning and for in-duct items such as coils, filters and attenuators.
  • Damper type, actuation and wiring are often settled only in the specification; raise them as RFIs if they are not.

On a ductwork tender, the duct itself is rarely what goes wrong. It is the items you count one at a time: the fire damper on a branch that crosses a corridor wall, the access door beside it, the motorised damper the specification upgraded. Each is a small line on the schedule and a real cost on site.

Count a fire damper wherever a duct passes through a fire-resisting wall or floor, count an access door at every fire damper, then add the access doors the specification and cleaning standards call for at other in-duct items. Read the damper type, size and actuation from the drawings and the specification, and raise anything they do not settle as an RFI.

What is a fire damper?

A fire damper is a device fitted in a duct where it passes through a fire-resisting wall or floor. When it detects heat, typically through a fusible link that melts at a set temperature, it closes and restores the fire resistance of the wall or floor the duct passes through.

TypeWhat it doesHow it closes
Fire damperStops fire passing through a fire-resisting wall or floorUsually a fusible link; sometimes a thermal actuator
Fire and smoke damperStops fire and limits smoke leakageMotorised, released by the fire alarm or a thermal device
Smoke damperControls smoke movement in a smoke control systemMotorised
Motorised damperOpens or closes for control, not fireActuator, controlled by the BMS
Volume control damper (VCD)Sets airflow for commissioningBy hand, locked in position
Damper types you will meet in a ductwork takeoff

Which standards apply to fire dampers?

  • UK and Europe: BS EN 15650 is the product standard for fire dampers; BS EN 1366-2 is the fire resistance test; BS EN 13501-3 gives the classification (for example E, EI and S ratings with a time in minutes).
  • US: UL 555 covers fire dampers and UL 555S smoke dampers; combination fire and smoke dampers are listed to both. NFPA 90A sets where they are required in air distribution systems.
  • Installation: a damper's fire rating holds only when it is installed as it was tested, so the manufacturer's installation frame or sleeve and fixing method belong in your price.

Where do ductwork access doors go?

Access doors, also called access panels, let people inspect, clean and maintain what is inside the duct. In the UK, DW/144 covers how they are made and placed, and BESA's TR19 guide to internal cleanliness of ventilation systems calls for access that lets the whole system be inspected and cleaned. A takeoff usually counts access doors:

  • At every fire damper and fire and smoke damper, so it can be inspected, tested and reset.
  • Beside in-duct equipment: motorised dampers, coils, filters, attenuators, fans and heaters.
  • For cleaning, where the specification asks for TR19 access, often at changes of direction and along long runs.
  • In kitchen extract ductwork, where cleaning access is usually specified more tightly.

How do you count fire dampers and access doors in a takeoff?

  1. 1

    Read the legend

    Find the symbols for fire dampers, fire and smoke dampers, smoke dampers and access doors. Some drawings show access doors; many leave them to the specification.

  2. 2

    Find every fire line

    Compartment walls and floors may be marked on the mechanical layouts or only on the architect's fire strategy drawings. Ask for them if they were not issued.

  3. 3

    Count dampers by type and size

    A damper is priced by type and duct size. A 400 x 300 fire damper and a 400 x 300 fire and smoke damper are different lines.

  4. 4

    Add access doors

    One at each fire damper, then those the specification asks for at other in-duct items and for cleaning, by size.

  5. 5

    Read the specification

    Note the damper standard, the fire rating, actuation (fusible link, 24 V or 230 V actuator), any drop test, BMS or fire alarm interface, and who wires them.

  6. 6

    Raise the RFIs

    Damper types the specification does not settle, fire lines not shown, and wiring or interfaces marked by others all belong in RFIs and your scope letter.

Can software count fire dampers and access doors?

Yes. Automated HVAC takeoff software can read the damper symbols from the legend, count them by type and size across every sheet, apply an access door rule for each, and read the specification for actuation and testing. Customiser does this and links each count back to the place on the drawing it came from, so your estimator can check it. See automated HVAC take-off.

Go further

FAQ

Questions about this topic

Short answers to what people ask next.

Contact us
  • Where a duct passes through a fire-resisting wall or floor, so that the wall or floor keeps its fire resistance. The building's fire strategy sets which walls and floors those are.

  • A fire damper stops fire passing through a fire-resisting wall or floor, usually closing on a fusible link. A fire and smoke damper also limits smoke leakage and is normally motorised, closing on a signal from the fire alarm.

  • Yes. Fire dampers must be inspected and tested, so each needs an access door beside it. Count them together.

  • TR19 is BESA's guide to the internal cleanliness of ventilation systems. Specifications refer to it for cleaning access and for how ductwork is cleaned and verified.